๐จ Steam Humidifier & Absorption
Calculate steam injection rates (kg/h), boiler power, and non-wetting absorption distance (m) to prevent duct condensation and mold growth per ASHRAE 62.1.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
Hvac
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
24
โก Solves
21
๐พ Downloads
342
๐ฆ Fortran Code
4.4 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
๐จ AHU Steam Dispersion Manifold & Non-Wetting Absorption Plume
Real-time visual simulation of steam micro-jet discharge & absorption distance envelope (D_abs)๐ Configuration & Presets
๐ข Office Winter (20% -> 45%)
๐ฅ Hospital ICU (6-Tube Grid)
๐งช Single Wand Tube (15% -> 40%)
๐ฐ Printing Press (60% RH)
ASHRAE 62.1 Formulations:
โข Steam Rate: mฬsteam = mฬair ยท (wโ โ wโ) ร 3600 [kg/h]
โข Absorption Distance: Dabs โ (1 / Ntubes0.75) ยท vair ยท [ (RHโ โ RHโ) / (100 โ RHโ) ]0.65 [m]
โข Electric Power: P = mฬsteam ยท hfg / 3600 [kW]
โข Steam Rate: mฬsteam = mฬair ยท (wโ โ wโ) ร 3600 [kg/h]
โข Absorption Distance: Dabs โ (1 / Ntubes0.75) ยท vair ยท [ (RHโ โ RHโ) / (100 โ RHโ) ]0.65 [m]
โข Electric Power: P = mฬsteam ยท hfg / 3600 [kW]
๐ Humidification Results
๐ Output Summary
Required Steam Injection Rate
mฬsteam = 15.32 kg/h (33.8 lb/h)
Moisture Gain: ฮw = 3.63 g/kg (15% โ 40% RH)
Dabs = 1.70 m
Non-Wetting Absorption Distance
1.70 meters
1 tube(s) @ 4.1 m/s
Electric Boiler Power Required
10.85 kW
37017 BTU/h
Air Velocity in Duct (vair)
4.05 m/s
797 FPM
Specific Humidity Ratio (wโ)
5.79 g/kg
Entering wโ = 2.16 g/kg
๐ Steam Output Rate (kg/h) vs Target RH (%)
๐ Absorption Distance (m) vs Number of Manifold Tubes
================================================================= THERMOFLUIDCALC โ STEAM HUMIDIFIER & ABSORPTION REPORT ================================================================= Case Title : Small Commercial Single Dispersion Tube Humidifier Air Volume Flow Rate (Q) : 3,500.0 m3/h (2,060 CFM) Duct Cross-Section (W x H) : 600 mm x 400 mm (v = 4.05 m/s) Entering / Target RH : 15.0 % -> 40.0 % RH (at 20.0 ยฐC DB) Dispersion Manifold Tubes : 1 tube(s) ----------------------------------------------------------------- STEAM INJECTION CAPACITY : 15.32 kg/h (33.77 lb/h) NON-WETTING ABSORPTION DIST: 1.70 meters (5.6 feet) Electric Boiler Power Draw : 10.85 kW (37017 BTU/h) Entering Humidity Ratio w1 : 2.16 g/kg Target Leaving Ratio w2 : 5.79 g/kg (ฮw = +3.63 g/kg) =================================================================
๐ Calculation Methodology & ASHRAE 62.1 Standards
Non-Wetting Absorption Distance
Visible steam plumes must fully absorb before reaching duct obstructions (elbows, filters, silencers) to prevent stagnant liquid pooling and biological mold growth:
Dabs โ (1 / Ntubes0.75) ยท vair ยท [ ฮRH / (100 โ RHโ) ]0.65
Multi-Tube Rapid Dispersion Grids
Distributing steam across multiple vertical headers with engineered precision nozzles shortens absorption distance by up to 75% compared to single-wand injection.
Key Engineering Assumptions
- Atmospheric dry saturated steam at $100^\circ\text{C}$ ($h_{fg} = 2257\,\text{kJ/kg}$).
- Electric resistive or electrode boiler thermal efficiency $\eta \approx 95\%$.
- Isothermal humidification process along dry bulb lines.