๐จ Steam Humidifier & Absorption
Calculate steam injection rates (kg/h), boiler power, and non-wetting absorption distance (m) to prevent duct condensation and mold growth per ASHRAE 62.1.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
Hvac
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
24
โก Solves
21
๐พ Downloads
342
๐ฆ Fortran Code
4.4 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
๐จ AHU Steam Dispersion Manifold & Non-Wetting Absorption Plume
Real-time visual simulation of steam micro-jet discharge & absorption distance envelope (D_abs)๐ Configuration & Presets
๐ข Office Winter (20% -> 45%)
๐ฅ Hospital ICU (6-Tube Grid)
๐งช Single Wand Tube (15% -> 40%)
๐ฐ Printing Press (60% RH)
ASHRAE 62.1 Formulations:
โข Steam Rate: mฬsteam = mฬair ยท (wโ โ wโ) ร 3600 [kg/h]
โข Absorption Distance: Dabs โ (1 / Ntubes0.75) ยท vair ยท [ (RHโ โ RHโ) / (100 โ RHโ) ]0.65 [m]
โข Electric Power: P = mฬsteam ยท hfg / 3600 [kW]
โข Steam Rate: mฬsteam = mฬair ยท (wโ โ wโ) ร 3600 [kg/h]
โข Absorption Distance: Dabs โ (1 / Ntubes0.75) ยท vair ยท [ (RHโ โ RHโ) / (100 โ RHโ) ]0.65 [m]
โข Electric Power: P = mฬsteam ยท hfg / 3600 [kW]
๐ Humidification Results
๐ Output Summary
Required Steam Injection Rate
mฬsteam = 37.94 kg/h (83.6 lb/h)
Moisture Gain: ฮw = 5.31 g/kg (30% โ 60% RH)
Dabs = 0.90 m
Non-Wetting Absorption Distance
0.90 meters
4 tube(s) @ 4.2 m/s
Electric Boiler Power Required
26.87 kW
91696 BTU/h
Air Velocity in Duct (vair)
4.17 m/s
820 FPM
Specific Humidity Ratio (wโ)
10.52 g/kg
Entering wโ = 5.22 g/kg
๐ Steam Output Rate (kg/h) vs Target RH (%)
๐ Absorption Distance (m) vs Number of Manifold Tubes
================================================================= THERMOFLUIDCALC โ STEAM HUMIDIFIER & ABSORPTION REPORT ================================================================= Case Title : Printing Press / Paper Mill High Humidity Atmosphere Air Volume Flow Rate (Q) : 6,000.0 m3/h (3,531 CFM) Duct Cross-Section (W x H) : 800 mm x 500 mm (v = 4.17 m/s) Entering / Target RH : 30.0 % -> 60.0 % RH (at 23.0 ยฐC DB) Dispersion Manifold Tubes : 4 tube(s) ----------------------------------------------------------------- STEAM INJECTION CAPACITY : 37.94 kg/h (83.64 lb/h) NON-WETTING ABSORPTION DIST: 0.90 meters (3.0 feet) Electric Boiler Power Draw : 26.87 kW (91696 BTU/h) Entering Humidity Ratio w1 : 5.22 g/kg Target Leaving Ratio w2 : 10.52 g/kg (ฮw = +5.31 g/kg) =================================================================
๐ Calculation Methodology & ASHRAE 62.1 Standards
Non-Wetting Absorption Distance
Visible steam plumes must fully absorb before reaching duct obstructions (elbows, filters, silencers) to prevent stagnant liquid pooling and biological mold growth:
Dabs โ (1 / Ntubes0.75) ยท vair ยท [ ฮRH / (100 โ RHโ) ]0.65
Multi-Tube Rapid Dispersion Grids
Distributing steam across multiple vertical headers with engineered precision nozzles shortens absorption distance by up to 75% compared to single-wand injection.
Key Engineering Assumptions
- Atmospheric dry saturated steam at $100^\circ\text{C}$ ($h_{fg} = 2257\,\text{kJ/kg}$).
- Electric resistive or electrode boiler thermal efficiency $\eta \approx 95\%$.
- Isothermal humidification process along dry bulb lines.