๐จ Duct Sizing & Static Regain
Size circular and rectangular air ducts using Equal Friction and Velocity methods, with Colebrook-White friction, aspect ratio checks, and equivalent diameters.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
19
โก Solves
17
๐พ Downloads
489
๐ฆ Fortran Code
4.4 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
๐จ HVAC Air Duct Flow Profile & Velocity Boundary Layer
Real-time visual simulation of rectangular & circular duct velocity streamlines๐ Configuration & Presets
๐ข Office Trunk (8000 mยณ/h)
๐๏ธ Hotel Quiet (3.5 m/s)
๐ณ Kitchen Hood (9 m/s)
๐ฅ Cleanroom (14k mยณ/h)
ASHRAE Duct Formulations:
โข Equivalent Diameter: De = 1.30 ยท (a ยท b)0.625 / (a + b)0.25
โข Friction Rate: ฮP/L = f ยท (ฯ vยฒ) / (2 De)
โข Velocity Pressure: Pv = ยฝ ฯ vยฒ [Pa]
โข Aspect Ratio: AR = max(a, b) / min(a, b) โค 4:1
โข Equivalent Diameter: De = 1.30 ยท (a ยท b)0.625 / (a + b)0.25
โข Friction Rate: ฮP/L = f ยท (ฯ vยฒ) / (2 De)
โข Velocity Pressure: Pv = ยฝ ฯ vยฒ [Pa]
โข Aspect Ratio: AR = max(a, b) / min(a, b) โค 4:1
๐ Sizing Results & Dimensions
๐ Output Summary
Recommended Commercial Duct Dimensions
ร 256 mm (DN250)
Equivalent Round Diameter: ร 256.3 mm (AR = 1.00:1)
3.50 m/s
Actual Friction Loss Rate (ฮP/L)
0.62 Pa/m
0.008 in.wg/100ft
Velocity Pressure (Pv)
7.4 Pa
Dynamic Head
Acoustic Velocity Classification
3.50 m/s
โ
Low Acoustic Noise (Offices / Bedrooms NC โค 30)
Volumetric Airflow in CFM
383 CFM
650 mยณ/h
๐ Equivalent Round Diameter vs Airflow Rate Q
๐ Friction Loss Rate (Pa/m) vs Air Velocity
================================================================= THERMOFLUIDCALC โ ASHRAE / SMACNA DUCT SIZING REPORT ================================================================= Case Title : Hotel Guest Room Acoustic Low-Noise Branch Duct Air Volume Flow Rate (Q) : 650.0 m3/h (383 CFM) Target Sizing Method : Velocity Method ----------------------------------------------------------------- Equivalent Round Diameter : 256.29 mm (ร 10.1 in) Air Velocity in Duct : 3.50 m/s (689 FPM) Velocity Dynamic Pressure : 7.37 Pa Friction Loss Rate (dP/L) : 0.617 Pa/m (0.0075 in.wg/100ft) =================================================================
๐ Calculation Methodology & ASHRAE Standards
Equal Friction & Huebscher Equivalence
The Equal Friction method maintains uniform pressure drop per unit length. The Huebscher formula computes rectangular ducts with equivalent flow capacity:
De = 1.30 ยท (a ยท b)0.625 / (a + b)0.25
Aspect Ratio & Noise Criteria
Rectangular ducts should maintain aspect ratio $AR \le 4:1$ to minimize sheet metal weight and prevent acoustic rumble generated by high velocity gradients.
Key Engineering Assumptions
- Standard air density $\rho = 1.204\,\text{kg/m}^3$ at $20^\circ\text{C}$ and $101.325\,\text{kPa}$.
- Galvanized steel absolute roughness $\epsilon = 0.09\,\text{mm}$.
- Standard commercial 25 mm dimensional increments applied for fabrication.