๐Ÿ’จ Duct Sizing & Static Regain

Size circular and rectangular air ducts using Equal Friction and Velocity methods, with Colebrook-White friction, aspect ratio checks, and equivalent diameters.

โšก Fortran 90 Engine Double Precision (IEEE 754) โœ“ ISO / ASME Validated
Duct Sizing & Static Regain Hvac
๐Ÿ“Š Solver Telemetry โ— ACTIVE
๐Ÿ‘๏ธ Views 19
โšก Solves 17
๐Ÿ’พ Downloads 489 ๐Ÿ“ฆ Fortran Code 4.4 KB
๐Ÿ“… Released Jun 2026
โฑ๏ธ Latency < 1 ms
โšก TOOLS & REPORTS:
๐Ÿ’พ Download Fortran 90

๐Ÿ’จ HVAC Air Duct Flow Profile & Velocity Boundary Layer

Real-time visual simulation of rectangular & circular duct velocity streamlines

๐Ÿ“ Configuration & Presets

๐Ÿข Office Trunk (8000 mยณ/h) ๐Ÿ›๏ธ Hotel Quiet (3.5 m/s) ๐Ÿณ Kitchen Hood (9 m/s) ๐Ÿฅ Cleanroom (14k mยณ/h)
โš™๏ธ Sizing Method & Cross-Section Shape
๐Ÿ’จ Air Flow & Target Constraints
1 CFM โ‰ˆ 1.699 mยณ/h
Standard: 0.8 to 1.2 Pa/m (0.1 in.wg/100ft)
Branches: 3โ€“5 m/s, Mains: 6โ€“8 m/s
If rectangular: solves height b
ASHRAE Duct Formulations:
โ€ข Equivalent Diameter: De = 1.30 ยท (a ยท b)0.625 / (a + b)0.25
โ€ข Friction Rate: ฮ”P/L = f ยท (ฯ vยฒ) / (2 De)
โ€ข Velocity Pressure: Pv = ยฝ ฯ vยฒ [Pa]
โ€ข Aspect Ratio: AR = max(a, b) / min(a, b) โ‰ค 4:1

๐Ÿ“Š Sizing Results & Dimensions

๐Ÿ“Š Output Summary
๐Ÿ’พ Fortran Source

Recommended Commercial Duct Dimensions
900 ร— 575 mm
Equivalent Round Diameter: ร˜ 772.6 mm (AR = 1.57:1)
8.29 m/s
Actual Friction Loss Rate (ฮ”P/L) 0.80 Pa/m 0.010 in.wg/100ft
Velocity Pressure (Pv) 41.4 Pa Dynamic Head
Acoustic Velocity Classification 8.29 m/s ๐Ÿšจ High Velocity (Industrial / Noise Attenuation Required)
Volumetric Airflow in CFM 8,240 CFM 14,000 mยณ/h

๐Ÿ“ˆ Equivalent Round Diameter vs Airflow Rate Q

๐Ÿ“‰ Friction Loss Rate (Pa/m) vs Air Velocity

=================================================================
 THERMOFLUIDCALC โ€” ASHRAE / SMACNA DUCT SIZING REPORT
=================================================================
Case Title                 : Hospital Surgical Suite / Cleanroom Primary Distribution
Air Volume Flow Rate (Q)   : 14,000.0 m3/h (8,240 CFM)
Target Sizing Method       : Equal Friction
-----------------------------------------------------------------
Equivalent Round Diameter  : 772.61 mm (ร˜ 30.4 in)
Rectangular Duct Size      : 900 x 575 mm (35.4 x 22.6 in)
Rectangular Aspect Ratio   : 1.57:1
Air Velocity in Duct       : 8.29 m/s (1633 FPM)
Velocity Dynamic Pressure  : 41.42 Pa
Friction Loss Rate (dP/L)  : 0.800 Pa/m (0.0098 in.wg/100ft)
=================================================================

๐Ÿ“˜ Calculation Methodology & ASHRAE Standards

Equal Friction & Huebscher Equivalence

The Equal Friction method maintains uniform pressure drop per unit length. The Huebscher formula computes rectangular ducts with equivalent flow capacity:

De = 1.30 ยท (a ยท b)0.625 / (a + b)0.25

Aspect Ratio & Noise Criteria

Rectangular ducts should maintain aspect ratio $AR \le 4:1$ to minimize sheet metal weight and prevent acoustic rumble generated by high velocity gradients.

Key Engineering Assumptions

  • Standard air density $\rho = 1.204\,\text{kg/m}^3$ at $20^\circ\text{C}$ and $101.325\,\text{kPa}$.
  • Galvanized steel absolute roughness $\epsilon = 0.09\,\text{mm}$.
  • Standard commercial 25 mm dimensional increments applied for fabrication.