๐ช Air Curtain Aerodynamics
Determine air curtain Foster Deflection Number (Dn), AMCA 220 aerodynamic sealing efficiency, doorway infiltration reduction, and heating/cooling energy saved.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
Hvac
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
43
โก Solves
34
๐พ Downloads
309
๐ฆ Fortran Code
4.4 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
๐ช Overhead Air Curtain Planar Jet Barrier & Deflection
Real-time visual simulation of downward turbulent jet resisting outdoor thermal & wind infiltration๐ Configuration & Presets
๐ Supermarket (H=2.8m, 11.5 m/s)
โ๏ธ Cold Storage (-20ยฐC / +20ยฐC)
๐ Loading Dock (H=4.5m, 20 m/s)
๐๏ธ Retail Quiet (8.5 m/s)
AMCA 220 Formulations:
โข Deflection Number: Dn = (ฯi bโ vโยฒ cos ฮฑ) / [ g Hยฒ |ฯo โ ฯi| + ยฝ Cp ฯo vwยฒ H ]
โข Sealing Efficiency: Eseal โ 70% to 85% in optimal range (0.15 โค Dn โค 0.40)
โข Thermal Energy Saved: Qsaved = Eseal ยท mฬinfilt ยท cp ยท |Ti โ To| [kW]
โข Deflection Number: Dn = (ฯi bโ vโยฒ cos ฮฑ) / [ g Hยฒ |ฯo โ ฯi| + ยฝ Cp ฯo vwยฒ H ]
โข Sealing Efficiency: Eseal โ 70% to 85% in optimal range (0.15 โค Dn โค 0.40)
โข Thermal Energy Saved: Qsaved = Eseal ยท mฬinfilt ยท cp ยท |Ti โ To| [kW]
๐ Air Curtain Performance Results
๐ Output Summary
Aerodynamic Sealing Efficiency
Eseal = 75.0 %
โ ๏ธ OVERPOWERED (Excessive Jet Spill & Turbulence)
Dn = 0.831
Thermal Energy Saved
259.17 kW
884331 BTU/h
Unprotected Infiltration
25,675 mยณ/h
15,112 CFM
Fan Electric Power Draw
0.71 kW
COPbarrier = 363.0
Air Curtain Discharge Flow
8,640 mยณ/h
2.5m wide ร 60mm
๐ Sealing Efficiency (%) vs Discharge Velocity
๐ Heating/Cooling Energy Saved (kW) vs Outdoor Temp
================================================================= THERMOFLUIDCALC โ AIR CURTAIN AERODYNAMICS REPORT ================================================================= Case Title : Industrial Cold Storage Freezer Door Thermal Barrier Doorway Dimensions (H x W) : 3.50 m x 2.50 m Nozzle Slot / Velocity : 60.0 mm / 16.00 m/s (Angle = 20.0ยฐ) Indoor / Outdoor Temp : -20.0 ยฐC / 20.0 ยฐC (ฮT = 40.0 ยฐC) Outdoor Cross Wind Speed : 1.00 m/s ----------------------------------------------------------------- Foster Deflection No (Dn) : 0.8308 Aerodynamic Barrier Status : โ ๏ธ OVERPOWERED (Excessive Jet Spill & Turbulence) SEALING EFFICIENCY (E_seal): 75.00 % Unprotected Infiltration : 25,675.2 m3/h (15,112 CFM) Thermal Energy Saved : 259.17 kW (884331 BTU/h) Fan Power Consumption : 0.71 kW (COP = 363.0) =================================================================
๐ Calculation Methodology & AMCA 220 Standards
Foster Deflection Criterion
The Deflection Number $D_n$ compares the downward planar jet momentum against the opposing transverse forces of thermal buoyancy and wind pressure:
Dn = (ฯi bโ vโยฒ cos ฮฑ) / [ g Hยฒ ฮฯ + ยฝ Cp ฯo vwยฒ H ]
Optimal Barrier Operation
When $0.15 \le D_n \le 0.40$, the air curtain reaches the floor with sufficient momentum to split cleanly, preventing up to 85% of conditioned air loss.
Key Engineering Assumptions
- Standard planar turbulent turbulent jet expansion angle $\approx 14^\circ$.
- Fan combined motor and aerodynamic efficiency $\eta = 60\%$.
- Outward nozzle discharge angle $\alpha = 15^\circ$ to counteract inward draft.